ANALYSIS AND DETECTION POSSIBILITY OF THE PARTIAL DISCHARGES IN AIR INSULATED MEDIUM VOLTAGE SWITCHGEAR USING TRANSIENT EARTH VOLTAGE DETECTION

Rafał Buczko

rafal.buczko@pl.abb.com
ABB Centrum Rozwoju Produktów i Technologii Średniego Napięcia – Przasnysz, (Poland)

Andrzej Sikora


Instytut Elektrotechniki Oddział Technologii i Materiałoznawstwa Elektrotechnicznego – Wrocław (Poland)

Abstract

Modern switchgear increasingly use polymeric materials as insulation. Despite its numerous advantages they have limited resistance to partial discharge corrosion in some cases. In this paper noninvasive methods Transient Erath Voltage (TEV) measurement is proposed to detect various forms of partial discharges in medium voltage switchgear. These method allows for non-invasive diagnostic without switch of the switchgear. Measurement results confirm the effectiveness of the proposed approach.


Keywords:

partial discharges, switchgear, transient earth voltage

Brown P.: Non-intrusive partial discharge measurements on high voltage switchgear, 1–5, 1996
  Google Scholar

Nakaoka T., Tai Y., Kamarol M., Kozako M., Hikita M.: Development of Partial Discharge Detection and Diagnostic Methods of Vacuum Circuit Breaker, 485–488, 2014
  Google Scholar

Reid A.J., Judd M.D., Duncan G.: Simultaneous Measurement of Partial Discharge Using TEV , IEC60270 and UHF Techniques, 439–442, 2012
  Google Scholar

Wang L., Ning W., Wang L., Lu H., Wang H., Jia S., Wu J.: Experimental Investigation of Partial Discharge Detection in Medium-voltage Switchgear Based on Ultra-High-Frequency Sensor, 2–5, 2013
  Google Scholar

Canadian Standards C22.2 No.193 - M1983: High voltage full-load interrupter switches
  Google Scholar

IEC 62271-102, 2013: High-voltage switchgear and controlgear - Part 102: Alternating current disconnector and earthing siwtches
  Google Scholar

IEC 62271-103, 2011: High-voltage switchgear and controlgear - Part 103: Switches for rated voltage above 1 kV up to and including 52 kV
  Google Scholar

IEC 62478, draft 2010: High voltage test techniques: Measurement of partial discharges by electromagnetic and acoustic methods
  Google Scholar

PN-EN 60270, 2003: Wysokonapięciowa technika probiercza. Pomiary wyładowań niezupełnych
  Google Scholar


Published
2016-08-08

Cited by

Buczko, R., & Sikora, A. . (2016). ANALYSIS AND DETECTION POSSIBILITY OF THE PARTIAL DISCHARGES IN AIR INSULATED MEDIUM VOLTAGE SWITCHGEAR USING TRANSIENT EARTH VOLTAGE DETECTION. Informatyka, Automatyka, Pomiary W Gospodarce I Ochronie Środowiska, 6(3), 70–74. https://doi.org/10.5604/20830157.1212272

Authors

Rafał Buczko 
rafal.buczko@pl.abb.com
ABB Centrum Rozwoju Produktów i Technologii Średniego Napięcia – Przasnysz, Poland

Authors

Andrzej Sikora 

Instytut Elektrotechniki Oddział Technologii i Materiałoznawstwa Elektrotechnicznego – Wrocław Poland

Statistics

Abstract views: 185
PDF downloads: 320