Indoor air quality in a preschool
Marek Telejko
Department of Building Engineering Technologies and Organization; Faculty of Civil Engineering and Architecture; Kielce University of Technology (Poland)
Abstract
The article presents the results of indoor air quality (IAQ) assessment in four local preschools. The natural ventilation system was used in the buildings. Outdoor air was supplied to the premises through a leak in the external walls and air intakes were of maximum efficiency of 30 m3/h. Parameters describing IAQ were measured, such as: temperature, relative humidity and carbon dioxide concentration. Two series of studies were performed in each preschool. On the basis of the survey, it can be clearly stated that the indoor air quality in preschools is considered to be very low very low. All the analyzed parameters describing the quality do not meet the current legal requirements. Reported values of CO2 concentration exceeded three times the value set of the recommended maximum.
Keywords:
building physics, ventilation, air exchange, indoor air quality, preschool buildingReferences
Piotrowski J. Telejko M. Zender-Świercz E., Wpływ szczelnej obudowy na dystrybucję powietrza wentylacyjnego, Energia i budynek 7/2010, s. 23-25
Google Scholar
Telejko M., Piotrowski J. Z., Zaburzenia wymiany powietrza w budynkach poddanych termomodernizacji - Fizyka budowli w teorii i praktyce, Sekcja Fizyki Budowli Komitetu Inżynierii Lądowej i Wodnej PAN, Łódź – Słok 2007, s. 291 - 296.
Google Scholar
Dz. U. Nr 75 z 2002 r., poz. 690 z dn. 12 kwietnia 2002 r. w sprawie warunków technicznych jakim powinny odpowiadać budynki i ich usytuowanie z późniejszymi zmianami, z późniejszymi zmianami
Google Scholar
PN-83/B-03430 Wentylacja w budynkach mieszkalnych zamieszkania zbiorowego i użyteczności publicznej. Wymagania, PKN, 1983
Google Scholar
PN-83/B-03430:Az03 Wentylacja w budynkach mieszkalnych zamieszkania zbiorowego i użyteczności publicznej. Wymagania. Zmiana Az3, PKN, 2000
Google Scholar
Dz. U. Nr 207 poz. 2016 z roku 2003, Ustawa z dn. 7 lipca 1994 Prawo Budowlane, z późniejszymi zmianami.
Google Scholar
Nantka, M.B., Wentylacja w budownictwie ogólnym – przegląd, działanie, problemy i mity, Materiały Forum Instalacyjnego, Poznań 2004
Google Scholar
Nowakowski, E., Problemy z wentylacją grawitacyjną pomieszczeń, Rynek Instalacyjny 9/02, s. 58-62
Google Scholar
Nantka M.B., Naturalna wymiana powietrza a szczelność mieszkań, Forum Wentylacja 2005, Warszawa 2005
Google Scholar
Sowa, J., Proces migracji zanieczyszczeń w warunkach stochastycznych zakłóceń, Praca doktorska, Wydział Inżynierii Środowiska Politechniki Warszawskiej, Warszawa 1995
Google Scholar
WHO Regional Office for Europe (2000), Air Quality Guidelines for Europe, SE 2000, Copenhagen, European Series, No. 91
Google Scholar
ASHRAE 62-1989 Ventilation for acceptable Indoor Air Quality.
Google Scholar
PN-EN 13779:2008 Wentylacja budynków niemieszkalnych – Wymagania dotyczące właściwości instalacji wentylacji i klimatyzacji, PKN 2008
Google Scholar
EN ISO 7730:2006, Ergonomia środowiska termicznego – Analityczne wyznaczanie i interpretacja komfortu termicznego z zastosowaniem obliczania wskaźników PMV i PPD, PKN 2006
Google Scholar
Authors
Marek TelejkoDepartment of Building Engineering Technologies and Organization; Faculty of Civil Engineering and Architecture; Kielce University of Technology Poland
Statistics
Abstract views: 252PDF downloads: 112
License
This work is licensed under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License.
Budownictwo i Architektura supports the open science program. The journal enables Open Access to their publications. Everyone can view, download and forward articles, provided that the terms of the license are respected.
Publishing of articles is possible after submitting a signed statement on the transfer of a license to the Journal.