Indoor air quality in a preschool

Dorota Koruba


Department of Building Physics and Renewable Energy; Faculty of Environmental Engineering, Geomatics and Power Engineering; Kielce University of Technology (Poland)
https://orcid.org/0000-0002-4092-0157

Ewa Zender-Świercz


Department of Building Physics and Renewable Energy; Faculty of Environmental Engineering, Geomatics and Power Engineering; Kielce University of Technology (Poland)
https://orcid.org/0000-0002-5684-8276

Jerzy Zb. Piotrowski


Department of Building Physics and Renewable Energy; Faculty of Environmental Engineering, Geomatics and Power Engineering; Kielce University of Technology (Poland)
https://orcid.org/0000-0002-8479-1406

Łukasz Orman


Department of Network and Sanitary Systems; Faculty of Environmental Engineering, Geomatics and Power Engineering; Kielce University of Technology (Poland)
https://orcid.org/0000-0002-2221-1824

Marek Telejko


Department of Building Engineering Technologies and Organization; Faculty of Civil Engineering and Architecture; Kielce University of Technology (Poland)

Abstract

The article demonstrates the results of research on the indoor air quality (IAQ) in one of chosen preschools. In such facilities, the standard solution is a system of natural ventilation. Only a small percentage of such buildings is equipped with a mechanical ventilation system with adjustable parameters of the microclimate. The article presents the results of indoor air quality in the local preschool located in Kielce. In the present facility natural ventilation system was used. Preliminary studies confirmed the poor quality of indoor air in a subjected building. During the study, two improvements aimed at improving air quality were proposed. The first improvement was to increase the supply air stream. The second one concerned the installation of equipment for the treatment of indoor air. The results indicate that under certain guidelines it is possible to improve indoor air quality. As an indicator of indoor air quality, concentration of carbon dioxide was adopted. In addition, microbiological tests were performed indoors.


Keywords:

building physics, ventilation, air exchange, indoor air quality, air exchange

Dz. U. Nr 75 z 2002 r., poz. 690 z dn. 12 kwietnia 2002 r. w sprawie warunków technicznych jakim powinny odpowiadać budynki i ich usytuowanie z późniejszymi zmianami, z późniejszymi zmianami
  Google Scholar

PN-83/B-03430 Wentylacja w budynkach mieszkalnych zamieszkania zbiorowego i użyteczności publicznej. Wymagania, PKN, 1983
  Google Scholar

PN-83/B-03430:Az03 Wentylacja w budynkach mieszkalnych zamieszkania zbiorowego i użyteczności publicznej. Wymagania. Zmiana Az3, PKN, 2000
  Google Scholar

Piotrowski J., Telejko M., Zender-Świercz E., Wpływ Szczelnej obudowy budynku na Dystrybucję powietrza wentylacyjnego, Energia i budynek 7/2010, s. 23 – 25
  Google Scholar

Telejko M., Piotrowski J. Z - Dystrybucja powietrza wentylacyjnego w budynkach ze szczelną obudową, Fizyka Budowli w Teorii i Praktyce, tom IV, s.183-186
  Google Scholar

Dz. U. Nr 207 poz. 2016 z roku 2003, Ustawa z dn. 7 lipca 1994 Prawo Budowlane, z późniejszymi zmianami
  Google Scholar

Nantka, M.B., Wentylacja w budownictwie ogólnym – przegląd, działanie, problemy i mity, Materiały Forum Instalacyjnego, Poznań 2004
  Google Scholar

Nowakowski, E., Problemy z wentylacją grawitacyjną pomieszczeń, Rynek Instalacyjny 9/2002, s. 58-62
  Google Scholar

WHO Regional Office for Europe (2000), Air Quality Guidelines for Europe, SE 2000, Copenhagen, European Series, No. 91
  Google Scholar

ASHRAE 62-1989 Ventilation for acceptable Indoor Air Quality.
  Google Scholar

PN-EN 13779:2008 Wentylacja budynków niemieszkalnych – Wymagania dotyczące właściwości instalacji wentylacji i klimatyzacji, PKN 2008
  Google Scholar

Popiołek Z. red., Energooszczędne kształtowanie środowiska wewnętrznego, Katedra Ogrzewnictwa, Wentylacji i Techniki Odpylania, Politechnika Śląska, Gliwice, 2005
  Google Scholar

Wargocki P., Wyon D., Matysiak B., Irgens S., The effects of classroom air temperature and outdoor air supply rate on performance of school work by children, Proceedings of Indoor Air 2005, The 10th International Conference on Indoor Air Quality and Climate, Beijing, China, 2005, pp. 368-372
  Google Scholar

PN-89/Z-04111, arkusz 01, Ochrona czystości powietrza. Badania mikrobiologiczne. Postanowienia ogólne i zakres normy.
  Google Scholar

PN-89/Z-04111 arkusz 02, Ochrona czystości powietrza. Badania mikrobiologiczne. Oznaczanie liczby bakterii w powietrzu atmosferycznym (imisja) przy pobieraniu próbek metodą aspiracyjną i sedymentacyjną.
  Google Scholar

PN-89/Z-04111. arkusz 03, Ochrona czystości powietrza. Badania mikrobiologiczne. Oznaczanie liczby bakterii grzybów pleśniowych mikroskopowych w powietrzu atmosferycznym (imisja) przy pobieraniu próbek metodą aspiracyjną i sedymentacyjną
  Google Scholar

Malicka D., Technologia oczyszczania powietrza Activtek, Polski Instalator 6/2010, s.78-79
  Google Scholar


Published
2014-12-09

Cited by

Koruba, D. (2014) “Indoor air quality in a preschool”, Budownictwo i Architektura, 13(4), pp. 007–013. doi: 10.35784/bud-arch.1682.

Authors

Dorota Koruba 

Department of Building Physics and Renewable Energy; Faculty of Environmental Engineering, Geomatics and Power Engineering; Kielce University of Technology Poland
https://orcid.org/0000-0002-4092-0157

Authors

Ewa Zender-Świercz 

Department of Building Physics and Renewable Energy; Faculty of Environmental Engineering, Geomatics and Power Engineering; Kielce University of Technology Poland
https://orcid.org/0000-0002-5684-8276

Authors

Jerzy Zb. Piotrowski 

Department of Building Physics and Renewable Energy; Faculty of Environmental Engineering, Geomatics and Power Engineering; Kielce University of Technology Poland
https://orcid.org/0000-0002-8479-1406

Authors

Łukasz Orman 

Department of Network and Sanitary Systems; Faculty of Environmental Engineering, Geomatics and Power Engineering; Kielce University of Technology Poland
https://orcid.org/0000-0002-2221-1824

Authors

Marek Telejko 

Department of Building Engineering Technologies and Organization; Faculty of Civil Engineering and Architecture; Kielce University of Technology Poland

Statistics

Abstract views: 264
PDF downloads: 131


License

Creative Commons License

This work is licensed under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License.

Budownictwo i Architektura supports the open science program. The journal enables Open Access to their publications. Everyone can view, download and forward articles, provided that the terms of the license are respected.

Publishing of articles is possible after submitting a signed statement on the transfer of a license to the Journal.